[170852] in Hotline Meeting

home help back first fref pref prev next nref lref last post

Approved: Bldg. 4 - Normal Building Power 480V Shutdown-bldg. 4

daemon@ATHENA.MIT.EDU (Jennifer Garland)
Thu Jul 18 12:46:17 2013

From: Jennifer Garland <jennygar@plant.mit.edu>
To: "jmletend@mit.edu" <jmletend@mit.edu>,
        "oconaill@mit.edu"
	<oconaill@mit.edu>,
        "DICKP@MIT.EDU" <DICKP@mit.edu>, "alz@MIT.EDU"
	<alz@mit.edu>,
        Jim Harrington <lordjim@mit.edu>, "laugh@mit.edu"
	<laugh@mit.edu>,
        "graham@mit.edu" <graham@mit.edu>, "abm@mit.edu"
	<abm@mit.edu>,
        "tommyl@mit.edu" <tommyl@mit.edu>, "myersm@MIT.EDU"
	<myersm@mit.edu>,
        "jdoughty@mit.edu" <jdoughty@mit.edu>,
        "swade@mit.edu"
	<swade@mit.edu>, "rjwilk@mit.edu" <rjwilk@mit.edu>,
        "Bales@mit.edu"
	<Bales@mit.edu>,
        "acalogge@mit.edu" <acalogge@mit.edu>,
        "slipnosk@mit.edu"
	<slipnosk@mit.edu>,
        "sharonp@mit.edu" <sharonp@mit.edu>,
        "OPS RM Campus
 Services Main" <rm-mcs@mit.edu>,
        Ops Custodial Admin & Support Staff
	<cust-staff@mit.edu>,
        "mbj@mit.edu" <mbj@mit.edu>, "blayne@mit.edu"
	<blayne@mit.edu>,
        "pbhouk@gmail.com" <pbhouk@gmail.com>, Gerry Hughes
	<ghughes@mit.edu>,
        "lechtman@mit.edu" <lechtman@mit.edu>,
        "Tarky@mit.edu"
	<Tarky@mit.edu>,
        "help@math.mit.edu" <help@math.mit.edu>,
        "pelletier@math.mit.edu" <pelletier@math.mit.edu>,
        "mottley@mit.edu"
	<mottley@mit.edu>, "thane@mit.edu" <thane@mit.edu>,
        "carleton@mit.edu"
	<carleton@mit.edu>,
        "smuto@MIT.EDU" <smuto@mit.edu>,
        "cubstead@MIT.EDU"
	<cubstead@mit.edu>,
        "cmodica@mit.edu" <cmodica@mit.edu>,
        MIT Schedules Office
	<schedules@mit.edu>,
        "scottide@MIT.EDU" <scottide@mit.edu>,
        "heatherg@mit.edu" <heatherg@mit.edu>,
        "shutdowns@mit.edu"
	<shutdowns@mit.edu>,
        "whomeyer@mit.edu" <whomeyer@mit.edu>,
        "ksemerj@mit.edu"
	<ksemerj@mit.edu>,
        Ops RM Shutdown <rm-shutdown@mit.edu>, DOF EHS
	<dof-ehs@mit.edu>,
        "cp-command@mit.edu" <cp-command@mit.edu>,
        "safety@mit.edu" <safety@mit.edu>, Operators <Operators@plant.mit.edu>,
        "DOF
 Customer Service Center" <dof-csc@mit.edu>,
        "Ops Custodial Admin & Support
 Staff" <cust-staff@mit.edu>
CC: "jennygar@mit.edu" <jennygar@mit.edu>, "mdeluga@mit.edu" <mdeluga@mit.edu>
Date: Thu, 18 Jul 2013 12:46:05 -0400
Message-ID: <4EEA516695C10541B7CB963FF54A56AF13C60AD342@dof-exchmbx01.facilities.ms.mit.edu>
Content-Language: en-US
Content-Type: text/plain; charset="us-ascii"
MIME-Version: 1.0
Content-Transfer-Encoding: 8bit

The following Approved Normal Building Power 480V Shutdown-bldg. 4 power panel DPH4GI-4-131A/B,146,159,163, lihgts/welding outlet, 8-101 lights, bldg. 31 dc power is on Friday, July 19, 2013 from 4:00am - 6:00am is for your information.  Any questions please contact Billy Homeyer x8-0432.



Thank you,

Jennifer M. Garland
Repair and Maintenance
4-4350

Type: Normal
Date: July 19, 2013
Day: Friday
Time: 4:00am - 6:00am
Building(s): bldg 4,8 and 31
Room(s): bldg. 4 power panel DPH4GI-4-131A/B,146,159,163, lihgts/welding outlet, 8-101 lights, bldg. 31 dc power
System: building power, lighting
Duration: 4:00am - 6:00am
Reason: 
We request a bldg 4 normal bldg power shutdown, 480V/277V power panel DPH4G1, located in 4-0041EE, from 4 AM to 6 AM on Friday morning, July 19th, 2013 for Bennett Electric (John Shaw 617-293-4806)  to install a 225A circuit breaker and tie-in the 480V-208V transformer for supplying the 4-270/370 classrooms with 500A of 208V power and as part of the 4-classrooms renovations phase of the 2 Chemistry renovation project by Bond Brothers (Jesse Conklin 617-938-4175). Marty Deluga 4-5081 and Joe Collins 3-3621 are the MIT project managers.

DPH4G1 feeds panels 1) LPH4131; only fan coil units in 4-131B affected 2) LPH413A only some welding lab welding specific outlets and the point of use hot water heater in the welding at the lab's sink 3) LH4G1 which feeds only the 4-1st floor corridor panel LH411 3A) LH411 feeds lighting in 4-131A and B and 8-101, some 4-1st floor long corridor lighting and lighting in rooms 4-146, 159 and 163 4) bldg 10-042 pp DP which feeds the rectifier for all DC power in bldg 31 


Effect: 
Loss of normal building power, lights and dc power for the duration of this shutdown. 