[56227] in Hotline Meeting
RE: Bldg. NW17 - Basement - Emergency Air Handler 2 Shutdown
daemon@ATHENA.MIT.EDU (David Shoemaker)
Wed Sep 5 06:38:17 2001
Message-Id: <5.1.0.14.2.20010905062553.02a36a10@ligo.mit.edu>
Date: Wed, 05 Sep 2001 06:30:46 -0400
To: Warren Scott <WScott@plant.mit.edu>, David Shoemaker <dhs@ligo.mit.edu>,
Andrea Nichols <andrea@plant.mit.edu>,
"'benford@space.mit.edu'" <benford@space.mit.edu>,
D-Zone <D-Zone@MIT.Edu>, "'dhs@tristan.mit.edu'" <dhs@tristan.mit.edu>,
"'fulton@psfc.mit.edu'" <fulton@psfc.mit.edu>,
"'hrycaj@pfc.mit.edu'" <hrycaj@pfc.mit.edu>,
"'shutdowns@mit.edu'" <shutdowns@MIT.Edu>,
"'cp-command@mit.edu'" <cp-command@MIT.Edu>
From: David Shoemaker <dhs@ligo.mit.edu>
Cc: "'shutdown@plant.mit.edu'" <shutdown@plant.mit.edu>,
"'rm-shutdown@mit.edu'" <rm-shutdown@MIT.Edu>,
Warren Scott <WScott@plant.mit.edu>, Mike Zucker <mike@ligo.mit.edu>,
Erik Katsavounidis <kats@ligo.mit.edu>, kbayer@ligo.mit.edu
In-Reply-To: <568F0AEE7A57D511923900508B55645174D6A6@PLANT.MIT.EDU>
Mime-Version: 1.0
Content-Type: multipart/alternative;
boundary="=====================_699155==_.ALT"
--=====================_699155==_.ALT
Content-Type: text/plain; charset="us-ascii"; format=flowed
Warren,
We'll talk this morning. What is crucial is to have an interim cooling
system which will carry the computer heat load in room 017 during the
repair (all other rooms could float up during a repair). Unfortunately, the
computing effort is running 24 hours/day until the 10th, it does need
cooling, so I also feel the strong need to fix it (and am sympathetic to
not wanting to leak HCFC).
thanks for getting back to me.
David
At 06:13 AM 9/5/2001, Warren Scott wrote:
>Please let us know when we can do this EMERGENCY repair. There is a
>refrigerant leak in that needs to be repair or we will be unable to meet
>the cooling needs of the basement area of NW17. We are also required by
>law to repair this leak to prevent the release of HCFC's into the atmosphere.
>
>We will accommodate you as best we can but would like to do this work ASAP.
>
>Warren Scott
>3-6328
>-----Original Message-----
>From: David Shoemaker [mailto:dhs@ligo.mit.edu]
>Sent: Tuesday, September 04, 2001 9:49 PM
>To: Andrea Nichols; 'benford@space.mit.edu'; D-Zone;
>'dhs@tristan.mit.edu'; 'fulton@psfc.mit.edu'; 'hrycaj@pfc.mit.edu';
>'shutdowns@mit.edu'; 'cp-command@mit.edu'
>Cc: 'shutdown@plant.mit.edu'; 'rm-shutdown@mit.edu'; Warren Scott; Mike
>Zucker; Erik Katsavounidis; kbayer@ligo.mit.edu
>Subject: Re: Bldg. NW17 - Basement - Emergency Air Handler 2 Shutdown
>
>
>
>THIS IS NOT ACCEPTABLE. WE HAVE AN INTERNATIONAL COLLABORATION SOFTWARE
>TEST UNDERWAY WHICH WILL RUN THROUGH THE 10 SEPTEMBER, AND ANY LOSS OF
>COOLING DURING THAT PERIOD WILL BE CATASTROPHIC FOR THE SCIENCE UNDERWAY.
>PLEASE CONTACT EITHER
>
>DAVID SHOEMAKER 617 253 6411, 617 283 5362
>MIKE ZUCKER 617 253 8070
>
>BEFORE ANY ACTION IS TAKEN.
>
>THANK YOU IN ADVANCE.
>
>DAVID SHOEMAKER, NW17 BASEMENT LAB DIRECTOR
>
>At 01:23 PM 9/4/2001, Andrea Nichols wrote:
>>To: benford@space.mit.edu; D-Zone; dhs@tristan.mit.edu; elk@mit.edu;
>>fulton@psfc.mit.edu; hrycaj@pfc.mit.edu; shutdowns@mit.edu;
>>cp-command@mit.edu
>>Cc: shutdown@plant.mit.edu; rm-shutdown@mit.edu; Warren Scott
>>Subject: Bldg. NW17 - Basement - Emergency Air Handler 2 Shutdown
>>
>>
>>
>>The following emergency air handler 2 shutdown for Bldg. NW17 - basement on
>>Wednesday, 9/5 is for your information. If you have any question about
>>this, please contact Warren Scott at 3-6328.
>>
>>Thank you.
>>
>>Andrea Nichols
>>Operations Center
>>8-7872
>>
>>Status: Emergency
>>Building: NW17 - Basement
>>Date: 9/5/2001
>>Day: Wednesday
>>Time: 7:30 AM - 3:30 PM
>>System: Air Handler 2
>>Duration: 8 hours
>>Reason:
>>Repair a refrigerant leak on evaporator.
>>
>>Effect:
>>Loss of Air Handler 2 in NW17 Basement. This means that no supply
>>ventilation, supply cooling, supply heating (off during summer) or
>>exhaust-general air will be operational during the emergency shutdown
>>period.
--=====================_699155==_.ALT
Content-Type: text/html; charset="us-ascii"
<html>
<font size=3>Warren, <br><br>
We'll talk this morning. What is crucial is to have an interim cooling
system which will carry the computer heat load in room 017 during the
repair (all other rooms could float up during a repair). Unfortunately,
the computing effort is running 24 hours/day until the 10th, it does need
cooling, so I also feel the strong need to fix it (and am sympathetic to
not wanting to leak HCFC). <br><br>
thanks for getting back to me. <br><br>
David<br><br>
<br>
At 06:13 AM 9/5/2001, Warren Scott wrote:<br>
</font><blockquote type=cite class=cite cite><font face="arial" size=2 color="#0000FF">Please
let us know when we can do this EMERGENCY repair. There is a
refrigerant leak in that needs to be repair or we will be unable to meet
the cooling needs of the basement area of NW17. We are also
required by law to repair this leak to prevent the release of HCFC's into
the atmosphere.</font><font size=3><br>
<br>
</font><font face="arial" size=2 color="#0000FF">We will accommodate you
as best we can but would like to do this work
ASAP.</font><font size=3><br>
<br>
</font><font face="arial" size=2 color="#0000FF">Warren Scott
</font><font size=3><br>
</font><font face="arial" size=2 color="#0000FF">3-6328</font><font size=3></font>
<dl><font face="tahoma" size=2>
<dd>-----Original Message-----
<dd>From:</b> David Shoemaker
[<a href="mailto:dhs@ligo.mit.edu" eudora="autourl">mailto:dhs@ligo.mit.edu</a>]
<dd>Sent:</b> Tuesday, September 04, 2001 9:49 PM
<dd>To:</b> Andrea Nichols; 'benford@space.mit.edu'; D-Zone;
'dhs@tristan.mit.edu'; 'fulton@psfc.mit.edu'; 'hrycaj@pfc.mit.edu';
'shutdowns@mit.edu'; 'cp-command@mit.edu'
<dd>Cc:</b> 'shutdown@plant.mit.edu'; 'rm-shutdown@mit.edu'; Warren
Scott; Mike Zucker; Erik Katsavounidis; kbayer@ligo.mit.edu
<dd>Subject:</b> Re: Bldg. NW17 - Basement - Emergency Air Handler 2
Shutdown<br><br>
</font><font size=3><br><br>
<dd>THIS IS NOT ACCEPTABLE. WE HAVE AN INTERNATIONAL COLLABORATION
SOFTWARE TEST UNDERWAY WHICH WILL RUN THROUGH THE 10 SEPTEMBER, AND ANY
LOSS OF COOLING DURING THAT PERIOD WILL BE CATASTROPHIC FOR THE SCIENCE
UNDERWAY. PLEASE CONTACT EITHER<br><br>
<dd>DAVID SHOEMAKER 617 253 6411, 617 283 5362
<dd>MIKE ZUCKER 617 253 8070<br><br>
<dd>BEFORE ANY ACTION IS TAKEN.<br><br>
<dd>THANK YOU IN ADVANCE. <br><br>
<dd>DAVID SHOEMAKER, NW17 BASEMENT LAB DIRECTOR<br><br>
<dd>At 01:23 PM 9/4/2001, Andrea Nichols
wrote:<blockquote type=cite class=cite cite>
<dd>To: <x-tab> </x-tab>benford@space.mit.edu;
D-Zone; dhs@tristan.mit.edu; elk@mit.edu;
<dd>fulton@psfc.mit.edu; hrycaj@pfc.mit.edu; shutdowns@mit.edu;
<dd>cp-command@mit.edu
<dd>Cc: <x-tab> </x-tab>shutdown@plant.mit.edu;
rm-shutdown@mit.edu; Warren Scott
<dd>Subject:
<x-tab> </x-tab>Bldg. NW17 -
Basement - Emergency Air Handler 2 Shutdown<br><br>
<br><br>
<dd>The following emergency air handler 2 shutdown for Bldg. NW17 -
basement on
<dd>Wednesday, 9/5 is for your information. If you have any
question about
<dd>this, please contact Warren Scott at 3-6328.<br><br>
<dd>Thank you.<br><br>
<dd>Andrea Nichols
<dd>Operations Center
<dd>8-7872<br><br>
<dd>Status: Emergency
<dd>Building: NW17 - Basement
<dd>Date: 9/5/2001
<dd>Day: Wednesday
<dd>Time: 7:30 AM - 3:30 PM
<dd>System: Air Handler 2
<dd>Duration: 8 hours
<dd>Reason:
<dd>Repair a refrigerant leak on evaporator.<br><br>
<dd>Effect:
<dd>Loss of Air Handler 2 in NW17 Basement. This means that no
supply
<dd>ventilation, supply cooling, supply heating (off during summer) or
<dd>exhaust-general air will be operational during the emergency
shutdown
<dd>period.</blockquote></font>