[54928] in Hotline Meeting
Bldg. E40 - all except Basement Computer Area - 5/22 - Air Handle
daemon@ATHENA.MIT.EDU (Andrea Nichols)
Tue May 8 08:57:15 2001
Message-ID: <82F0D564C5ADD31180EF00508B556451BD23D3@PLANT.MIT.EDU>
From: Andrea Nichols <andrea@PLANT.MIT.EDU>
To: "'adcruz@mit.edu'" <adcruz@mit.edu>,
"'rklester@mit.edu'"
<rklester@mit.edu>, E-Zone <E-Zone@mit.edu>,
"'gwj@mit.edu'"
<gwj@mit.edu>, "'jys@mit.edu'" <jys@mit.edu>,
"'kelley@mit.edu'"
<kelley@mit.edu>,
"'lambert@mit.edu'" <lambert@mit.edu>,
"'lrose@mit.edu'" <lrose@mit.edu>,
"'pmosley@mit.edu'" <pmosley@mit.edu>,
"'severino@mit.edu'" <severino@mit.edu>,
"'tdalton@mit.edu'"
<tdalton@mit.edu>,
"'shutdowns@mit.edu'" <shutdowns@mit.edu>,
"'jfob@mit.edu'" <jfob@mit.edu>, "'opsnote@mit.edu'" <opsnote@mit.edu>,
"'jdb@mit.edu'" <jdb@mit.edu>
Cc: "'shutdown@plant.mit.edu'" <shutdown@PLANT.MIT.EDU>
Date: Tue, 8 May 2001 08:57:08 -0400
MIME-Version: 1.0
Content-Type: text/plain
> To: adcruz@mit.edu; rklester@mit.edu; E-Zone; gwj@mit.edu; jys@mit.edu;
> kelley@mit.edu; lambert@mit.edu; lrose@mit.edu; pmosley@mit.edu;
> severino@mit.edu; tdalton@mit.edu; shutdowns@mit.edu; jfob@mit.edu;
> opsnote@mit.edu; jdb@mit.edu
> Cc: shutdown@plant.mit.edu
> Subject: Bldg. E40 - all except Basement Computer Area - 5/22 - Air
> Handler 1 Shutdown
>
>
The following Air Handler 1 shutdown request for Bldg. E40 with the
exception of the basement computer area on Tuesday, 5/22 is for your
information and comment. Would you please let me know whether this does or
does not meet with your approval.
Thanks very much,
Andrea Nichols
Operations Center
8-7872
> Status: Normal
> Building: E40 except for basement computer area
> Date: 5/22/2001
> Day: Tuesday
> Time: 7 AM - 3 PM
> System: Air Handler 1
> Duration: 8 hours
> Reason:
> To install oil trap and make it so it is more accessible for future
> maintenance.
>
> Effect:
> Loss of Air Handler 1 during the shutdown period. This means there will
> be no supply ventilation (air from outside), supply cooling, supply
> heating (from ceiling supply fans), exhaust-general air, compressed
> control air or chilled water (air conditioning) during the shutdown
> period.
>
>