[171483] in Hotline Meeting
Approved Bldg. 32 - Dreyfoos Stairwell Pressurization and General
daemon@ATHENA.MIT.EDU (Janine Findlay)
Wed Aug 14 08:55:32 2013
From: Janine Findlay <jfindlay@plant.mit.edu>
To: "mwf@mit.edu" <mwf@mit.edu>, "liscott@mit.edu" <liscott@mit.edu>,
"pwalsh@mit.edu" <pwalsh@mit.edu>,
"Kelley.kennedy@compass-USA.com"
<Kelley.kennedy@compass-USA.com>,
"myersm@MIT.EDU" <myersm@mit.edu>,
"jackc@csail.mit.edu" <jackc@csail.mit.edu>,
"jon@csail.mit.edu"
<jon@csail.mit.edu>,
"steverug@CSAIL.MIT.EDU" <steverug@csail.mit.edu>,
"lizaz@CSAIL.MIT.EDU" <lizaz@csail.mit.edu>,
"zue@csail.mit.edu"
<zue@csail.mit.edu>,
"isabell@mit.edu" <isabell@mit.edu>,
"sbleeb@mit.edu"
<sbleeb@mit.edu>,
Michael Fahie <mfahie@plant.mit.edu>,
"OPS RM Campus
Services Main" <rm-mcs@mit.edu>,
"Martin O'Brien" <mobrien@plant.mit.edu>,
"Stata-Custodial@mit.edu" <Stata-Custodial@mit.edu>,
Ops CSG All
<csg-all@mit.edu>, "jonesb@MIT.EDU" <jonesb@mit.edu>,
"dwright@MIT.EDU"
<dwright@mit.edu>,
"stata-desk@mit.edu" <stata-desk@mit.edu>,
"conferences-www@mit.edu" <conferences-www@mit.edu>,
"scheruku@MIT.EDU"
<scheruku@mit.edu>,
"dgeraci@mit.edu" <dgeraci@mit.edu>, "rosko@mit.edu"
<rosko@mit.edu>,
Michael Smith <masmith@mit.edu>, "willer@mit.edu"
<willer@mit.edu>,
"awolpert@mit.edu" <awolpert@mit.edu>, "edel@mit.edu"
<edel@mit.edu>,
"shanlon@mit.edu" <shanlon@mit.edu>,
"gillooly@MIT.EDU"
<gillooly@mit.edu>,
"lrbrutti@mit.edu" <lrbrutti@mit.edu>,
"rcruz@mit.edu"
<rcruz@mit.edu>, "aneely@mit.edu" <aneely@mit.edu>,
"wayneb@mit.edu"
<wayneb@mit.edu>,
MIT Schedules Office <schedules@mit.edu>,
"k_brown@MIT.EDU"
<k_brown@mit.edu>,
"monaglek@MIT.EDU" <monaglek@mit.edu>,
"kdonaher@mit.edu"
<kdonaher@mit.edu>,
"kasabula@mit.edu" <kasabula@mit.edu>,
"rpittari@mit.edu"
<rpittari@mit.edu>,
"ksimons@mit.edu" <ksimons@mit.edu>,
"rwong@brighthorizons.com" <rwong@brighthorizons.com>,
"worklife@mit.edu"
<worklife@mit.edu>,
"shutdowns@mit.edu" <shutdowns@mit.edu>,
"whomeyer@mit.edu" <whomeyer@mit.edu>,
"ksemerj@mit.edu" <ksemerj@mit.edu>,
Ops RM Shutdown <rm-shutdown@mit.edu>,
"cp-command@mit.edu"
<cp-command@mit.edu>,
"safety@mit.edu" <safety@mit.edu>,
Operators
<Operators@plant.mit.edu>,
DOF Customer Service Center <dof-csc@mit.edu>,
"Ops Custodial Admin & Support Staff" <cust-staff@mit.edu>
CC: "kdiggans@mit.edu" <kdiggans@mit.edu>
Date: Wed, 14 Aug 2013 08:55:18 -0400
Message-ID: <4EEA516695C10541B7CB963FF54A56AF13C69DE815@dof-exchmbx01.facilities.ms.mit.edu>
Content-Language: en-US
Content-Type: text/plain; charset="us-ascii"
MIME-Version: 1.0
Content-Transfer-Encoding: 8bit
The following approved supply fans 1 & 6 and exhaust fans 5 & 17 shutdown for Bldg. 32 - Dreyfoos Stairwell Pressurization and General Exhaust for Floors 1 - 9, on Tuesday, August 20, 2013, 6:00am - 4:00pm, is for your information. Any questions, please contact Billy Homeyer, x8-0432.
Thank you,
Jani Findlay
Comprehensive Stewardship Group
Dept. of Facilities
x3-6381
Type: Normal
Date: August 20, 2013
Day: Tuesday
Time: 6:00am - 4:00pm
Building(s): 32
Room(s): Dreyfoos Stairwell Pressurization and General Exhaust for Floors 1 - 9
System: Supply Fan 1 & 6, and Exhaust Fans 5 & 17
Duration: 10 hours
Reason:
Original: We request bldg 32-SF1, SF6 and EF5 shutdowns from 6 AM to 2 PM on Tuesday, July 16th, 2013 for relocating these fans on the Dreyfoos roof as part of the 32 roof repair project by Consigli Construction (Carlin Grenier 508-5509-2935). Keith Diggans 4-6174 is the MIT project manager.
When we bump SF1 and SF6 to check for rotation after they've been relocated, we will cause a momentary fire alarm system trouble. Carlin Grenier from Consigli Construction will call the OPS Center prior to the fans start asking for a trouble disregard. The trouble will clear itself when the fans are stopped. MIT CSG HVAC will be on-site when this happens and note the stairwell pressurization fans are normally off.
SF1 is the stairwell pressurization fan for stairwell 1
SF6 is listed as the pressurization fan for the vestibule
EF5 is listed as general exhaust for floors 1-9
*Extended and Modified - We would like to extend and modify the bldg 32-SF1,SF6 and EF5 shutdowns to include EF17 from 6 AM to 4 PM on Tuesday, August 20th, 2013 to install permanent power to equipment and disconnect & remove old temporary power as part of the 32-roof repair project by Consigli Construction (Carlin Grenier 508-509-2935). Keith Diggans 4-6174 is the MIT project manager. Both the shutdown request form and work order #5201146 have been modified to reflect this extension on behalf of Billy Homeyer.
Effect:
Loss of Dreyfoos Stairwell Pressurization and General Exhaust for Floors 1 - 9 for the duration for the shutdown.