>     I happened to look in on the Athena cluster in the 14 bsmt and
> found the room at 90 deg with both Chill water valves not open.
> I then pulled off the tstat and found quite a bit of oil in the control
> air
> both tstats were junk. I jumped out the air for full cooling but did not
> get back to replace the two Powers DA tstats. I have a work order in to
> myself to replace the tstats but if want to get it done the number 
> on maximo is 92024. The FCU's were discharging 59 deg when I 
> left for other calls.
> 	