[45635] in Hotline Meeting

home help back first fref pref prev next nref lref last post

Bldg. E52 Shutdown Request for 11/5

daemon@ATHENA.MIT.EDU (Andrea Nichols)
Fri Oct 30 09:12:02 1998

From: Andrea Nichols <andrea@PLANT.MIT.EDU>
To: "'schedule@mit.edu'" <schedule@MIT.EDU>,
        "'lhill@mit.edu'"
	 <lhill@MIT.EDU>,
        "'michaela@mit.edu'" <michaela@MIT.EDU>, "'gwj@mit.edu'" <gwj@MIT.EDU>,
        "'maureen@mit.edu'" <maureen@MIT.EDU>,
        "'jbkalb@mit.edu'" <jbkalb@MIT.EDU>,
        "'mscoppa@mit.edu'"
	 <mscoppa@MIT.EDU>,
        "'shutdowns@mit.edu'" <shutdowns@MIT.EDU>
Cc: "'shutdown@plant.mit.edu'" <shutdown@plant.mit.edu>
Date: Fri, 30 Oct 1998 09:03:36 -0500

> To: 	schedule@mit.edu; lhill@mit.edu; michaela@mit.edu; gwj@mit.edu;
> maureen@mit.edu; jbkalb@mit.edu; mscoppa@mit.edu; shutdowns@mit.edu
> Cc: 	shutdown@plant.mit.edu
> Subject: 	Bldg. E52 Shutdown Request for 11/5
> 
> 
The following shutdown request for Bldg. E52 on 11/5 is for your review
and comment. Would you please let me know whether or not this shutdown
has your approval.

Thanks very much.

Andrea Nichols
Operations Center
8-7872

> Status: Normal
> Building: E52
> Date: 11/5/98
> Day: Thursday
> Time: 5 AM - 8 AM
> System: Compressed control air, supply ventilation, supply cooling and
> supply heating
> Duration: 3 hours
> Reason: 
> Install oil filter on air dryers - remove old one. 
> 
> Effect: 
> Loss of supply ventilation (general air from outside), supply cooling
> (air conditioning) and supply heating (heating) as well as compressed
> control air during 3-hour shutdown.
> 
> 

home help back first fref pref prev next nref lref last post