The following shutdown request for Bldg. E52 on 11/5 is for your review
and comment. Would you please let me know whether or not this shutdown
has your approval.
Thanks very much.
Andrea Nichols
Operations Center
8-7872
> Status: Normal
> Building: E52
> Date: 11/5/98
> Day: Thursday
> Time: 5 AM - 8 AM
> System: Compressed control air, supply ventilation, supply cooling and
> supply heating
> Duration: 3 hours
> Reason:
> Install oil filter on air dryers - remove old one.
>
> Effect:
> Loss of supply ventilation (general air from outside), supply cooling
> (air conditioning) and supply heating (heating) as well as compressed
> control air during 3-hour shutdown.
>
>