[45280] in Hotline Meeting

home help back first fref pref prev next nref lref last post

RE: Case 122891: FW: Bldgs. 16 and 56 7th Floor Emergency Power S

daemon@ATHENA.MIT.EDU (Andrea Nichols)
Thu Oct 8 10:28:21 1998

From: Andrea Nichols <andrea@PLANT.MIT.EDU>
To: "'hotline@MIT.EDU'" <hotline@MIT.EDU>
Date: Thu, 8 Oct 1998 10:20:43 -0400

I checked with the person who will be performing this work --Charles
said the answer is "no".  The shutdown will affect only the 7th floor on
Bldgs. 16 and 56.
  Andrea

> ----------
> From: 	hotline@MIT.EDU[SMTP:hotline@MIT.EDU]
> Sent: 	Thursday, October 08, 1998 10:01 AM
> To: 	Andrea Nichols
> Subject: 	Case 122891: FW: Bldgs. 16 and 56 7th Floor Emergency
> Power Shutdown Request for 10/20
> 
> Case 122891 has been recently updated and currently stands as follows:
> 
> -----------
> 
> --- Entry: Thursday, Oct 08, 1998 8:33 AM     -- Email Received --
> -----------------------------------
> Date: Thu, 8 Oct 1998 08:26:02 -0400
> To: "'opsnote@mit.edu'" <opsnote@MIT.EDU>
> From: Andrea Nichols <andrea@PLANT.MIT.EDU>
> Cc: "'shutdowns@mit.edu'" <shutdowns@MIT.EDU>
> Subject: FW: Bldgs. 16 and 56 7th Floor Emergency Power Shutdown
> Request f	or
> 10/20
> 
> Dear opsnote:
> I have been informed that the above shutdown request for Bldgs. 16 and
> 56 - 7th Floor Emergency Power will affect the Bldg. 16 Tel Closets
> which affect the telephone and network systems.
> 
> FYI.
> Andrea Nichols
> 
> > ----------
> > From: 	Andrea Nichols
> > Sent: 	Wednesday, October 07, 1998 11:09 AM
> > To: 	'mparker@mit.edu'; 'shutdowns@mit.edu'
> > Cc: 	Shutdown
> > Subject: 	Bldgs. 16 and 56 7th Floor Emergency Power Shutdown
> > Request for 10/20
> > Importance: 	High
> > 
> > > To: 	mparker@mit.edu; shutdowns@mit.edu
> > > Cc: 	shutdown@plant.mit.edu
> > > Subject: 	Bldgs. 16 and 56 7th Floor Emergency Power Shutdown
> > > Request for 10/20
> > > 
> > > 
> > The following shutdown request for Bldgs. 16 and 56 (Emergency
> Power)
> > on
> > 10/20 is for your information and comment. Would you please let me
> > know
> > whether this has your approval or does not. 
> > 
> > Thanks Marshall.
> > 
> > Andrea Nichols
> > Operations Center
> > 8-7872
> > 
> > > Status: Normal
> > > Building: 16 and 56 - 7th floor only
> > > Date: 10/20/98
> > > Day: Tuesday
> > > Time: 7:00 AM - 9:00 AM
> > > System: Emergency Power
> > > Duration: 2 hours
> > > Reason: 
> > > To change tops on transformers
> > > 
> > > Effect: 
> > > Loss of emergency power: elevators and lighting (corridors and
> > > stairs). Air in these buildings will be affected as follows:
> > >  HVAC Controls:
> > > Offices: 
> > > Heating, cooling and ventilation devices (valves and dampers) will
> > > remain in their last commanded position (ie; if heat or cooling is
> > on
> > > it will stay on, if off it will stay off, ventilation levels will
> > stay
> > > the same).
> > > 
> > > All other spaces, including labs and corridors:
> > > Heating valves will go on full, cooling valves will go off, hood
> > > exhaust and make-up will stay at their last commanded position.
> We
> > > will be able to minimize the impact of full heat by lowering the
> > > heating water temperature as required.
> > > 
> > > 
> > > 
> > 
> 
> 
> 
> --- Entry: Thursday, Oct 08, 1998 10:01 AM    -- jjmorey --- 
> --- Sent E-Mail (Entire Log) To: ANDREA@PLANT.MIT.EDU
> 
> will this interfer with the network service for 56-129?
> 

home help back first fref pref prev next nref lref last post