[42171] in Hotline Meeting
FW: Approved -W91 - All - Electric Power and lighting Shutdown
daemon@ATHENA.MIT.EDU (Andrea Nichols)
Mon Mar 2 12:17:15 1998
From: Andrea Nichols <andrea@PLANT.MIT.EDU>
To: "'dcarlson@mit.edu'" <dcarlson@MIT.EDU>,
"'cappucci@mit.edu'"
<cappucci@MIT.EDU>,
"'jfreeman@mit.edu'" <jfreeman@MIT.EDU>,
"'mmahoney@mit.edu'" <mmahoney@MIT.EDU>, D-Zone <D-Zone@MIT.EDU>,
Neil Tomlinson <NTomlins@PLANT.MIT.EDU>,
James Sullivan
<jsulliva@PLANT.MIT.EDU>,
Manuel Moreira <mmoreira@PLANT.MIT.EDU>
Cc: "'shutdown@plant.mit.edu'" <shutdown@plant.mit.edu>,
"'cust-coach@mit.edu'" <cust-coach@MIT.EDU>,
RM-Support
<RM-Support@MIT.EDU>,
"'opsnote@mit.edu'" <opsnote@MIT.EDU>,
"'shutdown@mit.edu'" <shutdown@MIT.EDU>
Date: Mon, 2 Mar 1998 12:14:45 -0500
The following approved Electric Power and Lighting Shutdown for Bldg.
W91 on 3/5 is for your information.
Andrea Nichols
Operations Center
8-7872
> > Status: Normal
> > Building: W91 - All
> > Date: 3/5/98
> > Day: Friday
> > Time: 5:00 PM - 10:00 PM
> > System: All electric power and lighting (new UPS will power the main
> > machine room)
> > Duration: 5 hours
> > Reason:
> > To test new electrical switchgear and emergency generator.
> >
> > Effect:
> > Loss of Power: access controls, bldg. power, elevators, computers,
> > telephones and lighting; Water: chilled water and condenser water:
> Emergency Power will remain on as will lighting for corridors and
> stairs.
> > Air: supply ventilation, supply cooling, supply heating, exhaust
> > general, exhaust toilet and compressed control air; Steam:
> condensate
> > return.
> >
> >
>