Bldg. 1 - All and Bldg. 3 - three IS&T closets (357T, 259T, & 085T), Normal Building Power Shutdown Request
daemon@ATHENA.MIT.EDU (shutdown-response@MIT.EDU)
Fri May 25 13:36:04 2012
From: shutdown-response@MIT.EDU
To: <undisclosed_recipients@MIT.EDU>
Cc: <rlucas@MIT.EDU>
Date: Fri, 25 May 2012 13:35:58 -0400
Message-ID: <AB8306B01ED843328EBC93CF8F34836A@facilities.ms.mit.edu>
MIME-Version: 1.0
Content-Type: text/plain;
charset="iso-8859-1"
Content-Transfer-Encoding: 7bit
Content-Class: urn:content-classes:message
The following normal building power shutdown request for Bldg. 1 - All, and Bldg. 3 - three IS&T closets (357T, 259T, & 085T), on Thursday, June 14, 2012, at 9:00pm through 7:00am on Friday, June 15, 2012. Any questions, please contact Rich Lucas, x4-6801.
Please let us know whether this does or does not have your approval.
Thank you,
Jani Findlay
Repair and Maintenance
x3-6381
Type: Normal
Date: June 14, 2012
Day: Thursday
Time: 9:00pm (6/14) - 7:00am (6/15)
Building(s): 1 & 3
Room(s): 1 - All, 3 - three IS&T closets (357T, 259T, & 085T)
System: Normal Building Power
Duration: 10 hours
Reason:
A shutdown in requested for all normal power and lighting in building 1 in order to repair one cable and do preventative maintenance in the two electrical substations. This shutdown will also affect three IS&T closets in bldg 3 (rooms 3-357T, 3-259T and 3-085T), but John Morgante is aware of it.
Emergency Power will remain active.
In order to keep equipment safe guarded during the power down and re-energizing back up, IS&T will need to power down all equipment starting between 8-8:30 Thursday evening 6/14, and power back on at 7am on 6/15.
Bldg 1 will lose IS&T services; Wired network, Wireless, and VoIP. Bldg 3 will lose same services on the Killian Courtyard long corridor side, basement through 4th floor.
If you have any questions, please contact Rich Lucas, Sr. Electrical Engineer, MIT Department of Facilities - Utilities, phone: 617-324-6801.
Effect:
Loss of access controls, building power, elevators, computers, telephones, lighting (including corridors/stairs), chilled water, condenser water, supply ventilation/cooling/heating air, laboratory/general/toilet exhaust, compressed control/lab air, condensate return, and exhaust hoods for the duration of the shutdown.