[2033] in SIPB-AFS-requests

home help back first fref pref prev next nref lref last post

Re: Power layout in machine room

daemon@ATHENA.MIT.EDU (ghudson@MIT.EDU)
Sun Jun 25 01:41:15 1995

From: ghudson@MIT.EDU
Date: Sun, 25 Jun 1995 01:41:00 -0400
To: ghudson@MIT.EDU
Cc: star-maintainers@MIT.EDU
In-Reply-To: "[4033] in RTFM_Maintainers_Archive"


Tonight's W20 outage did not go according to plan.  Power in the
machine room was out for 20-30 minutes, and we had to shut down all of
the SIPB server machines instead of just the Maxines.  beacon and bed
were cleanly shut down; penguin-lust, anxiety-closet, and charon went
down forceably when one of our UPSs ran out.  I have also heard
reports that power went out in two or three other buildings besides
W20, but I don't know what went wrong.

penguin-lust finished running all ten of its nightly-jobs in under
three minutes before it was shut down.  charon stopped in the middle
of the Central America run; I moved /usr/spool/ca/data to
/usr/spool/ca/data.abortive, moved /usr/spool/ca/data.old to
/usr/spool/ca/data, removed /usr/spool/ca/ca_lock, and restarted
nightly_jobs (also nuking /etc/nightly_jobs.pid).

Since picayune's outage was anticipated, its nightly-jobs run was
postponed until after power was restored.

Our power configuration is now:

	* UPS 1: charon and 18.70 repeater (three plugs)
	* UPS 1: anxiety-closet and 18.181 repeater (two plugs)
	* UPS 1: penguin-lust (two plugs)
	* UPS 1: bloom-beacon (four plugs)
	* UPS 2: senator-bedfellow (five plugs)
	* UPS 2: rosebud (three plugs)
	* UPS 2: ronald-ann (five plugs, eight-plug strip)
	* UPS 2: picayune (two plugs)

After talking with Tom Coppeto, I elected to put the Maxine CPUs on
the UPSs.  Although the risk of not autobooting after a power outage
is increased, it does decrease the risk of damaging the machines
during a brownout.  We will be losing power in the machine room again
some time between 5am and 8am tonight; I asked Tom to make sure the
Maxines come up after that.

When I left W20, the lights on the fifth floor were still out.  We
have two six-outlet power strips on the outside table across from the
maxines, which should be brought into the office.  We also have a
power supply for the modem (which has not been plugged into the modem
for some time), which was running under the floor.  The modem is still
in the corner; the power supply is either on the floor or on the same
table as the power strips.  It should be put in a cabinet.


home help back first fref pref prev next nref lref last post