[94592] in North American Network Operators' Group
Re: Westin Seattle Outage?
daemon@ATHENA.MIT.EDU (chuck goolsbee)
Sat Jan 27 10:24:44 2007
In-Reply-To: <Pine.LNX.4.44.0701262321230.1759-100000@samwise.w-link.net>
Date: Sat, 27 Jan 2007 07:23:30 -0800
To: nanog@merit.edu
From: chuck goolsbee <chucklist@forest.net>
Errors-To: owner-nanog@merit.edu
>there was a power test of some kind, and a generator flaked or
>something. I've requested more detailed info, but have yet to receive it.
>From what I understand, it affected more than just one provider.
Here's the RFO I saw late last night:
During a planned generator test that was being performed by Westin
building maintenance, a bad battery resulted in the inability of the
back up system to hold power during the transition from commercial
power to generator power. This resulted in a service interruption
that lasted approximately 7 minutes (22:00PT - 22:07PT).
Before the problem could be isolated, building management switched
the power back from generator to commercial power resulting in
another service interruption that lasted approximately 8 minutes
(23:43PT - 23:51PT).
Still trying to find out what happened with XO.
--chuck