Re: MAE-East still no generator

daemon@ATHENA.MIT.EDU (Avi Freedman)
Sun Sep 8 10:00:23 1996

From: Avi Freedman <freedman@netaxs.com>
To: nathan@netrail.net (Nathan Stratton)
Date: Sun, 8 Sep 1996 09:58:10 -0400 (EDT)
Cc: stuart@pa.dec.com, alan@gi.net, perry@piermont.com, asp@partan.com,
        nanog@merit.edu
In-Reply-To: <Pine.LNX.3.95.960908090743.19899G-100000@netrail.net> from "Nathan Stratton" at Sep 8, 96 09:13:45 am

> Ok, I am not opening the GraybaR Power & Protection catalog.....
> 
> Page 12-31 Square D Company
> 
> Modle#		Power Raiting	Input 	Output			Dimensions
> 6154-02		500 VA		-48 VDC	120/220/230/240 VAC	7x17x15
> 6114-02		1 kVA		-48 VDC	120/220/230/240 VAC	7x17x15
> 6115-02		2 kVA		-48 VDC	120/220/230/240 VAC	17.5x17x15
> 6224-02		3 kVA		-48 VDC	120/220/230/240	VAC	17.5x17x15
> 
> Nathan Stratton		  CEO, NetRail, Inc.    Tracking the future today!

They told me the above would only work with "negative-ground" power,
and that it specifically would not work with telco -48vdc which was
configured as positive-ground.

Avi