On Wed, Mar 19, 2014 at 9:07 AM, Lamar Owen <lowen@pari.edu> wrote:
> 2011 NEC article 210.23(A) permits 15A receptacles on 20A branch circuits;
> 30A branch circuits must use 30A receptacles. If the OP's 30A branch
> circuit has an L6-20R on it then this would be a violation; see NEC Table
> 210.24 for a summary of the code.
Hi Lamar,
Nobody is talking about putting an L6-20R on a 30 amp circuit. OP was
talking about putting an L6-30P on a 20 amp appliance: a PDU that has
its own 20 amp breaker. Big difference.
Regards,
Bill Herrin
--