> > Regardless of generator sizing issues or disparities, if the ATS fails,
> > then no amount of grid or generator power will keep the cabinets juiced=
up.
That is patently false.
Assume N+1 UPS, with each UPS module having its own ATS fed from a utility =
and emergency bus. Then you can even individually maintain each UPS module =
and ATS. Bonus and score.
And if it's a really good place, you have two of the above (2(n+1)) and eac=
h of your power cords goes to one each.