On May 7, 2009, at 7:25 AM, Deric Kwok <deric.kwok2000@gmail.com> wrote:

> Hi all
>
> Any suggestion about data center
>
> 1/ to put on the switch in rack?
>
> eg: top. middle or bottom position
>
> 2/ There is no raise floor
> - adv
> - disadv
>
> Thank you for your information

We like to see switch gear in the top of the rack and exhausting put  
the back (provided it doesn't have side to side air flow)

Not having raised floor doesn't matter so long as cooling is delivered  
properly to the racks (top down, in row, or in rack), and cable  
management is available above the rack (ladder, trough, or rack-top  
like APC offers)