jcurran@mail.com (John Curran) writes:
> Also, you're still going to want to size the power drop so that
> the measured load won't exceed 80% capacity due to code.
that's true of output breakers, panel busbars, and wire. on the other
hand, transformers (e.g., 480->208 or 12K->480) are rated at 100%, as
are input breakers and of course generators.
--
Paul Vixie