E40 machine Rm. too cold

daemon@ATHENA.MIT.EDU (jchase@Athena.MIT.EDU)
Mon Jun 8 13:43:55 1992

From: jchase@Athena.MIT.EDU
To: hotline@Athena.MIT.EDU, network@Athena.MIT.EDU, op@Athena.MIT.EDU
Date: Mon, 08 Jun 92 13:43:33 EDT


   Physical Plant was dispatched to the e40 machine room @~ 12:15pm
   today. The alarm message was "too cold". I belive the temp is
   59 deg at the far (hallway) wall.

   The HVAC person said the cold water does not completly shut 
   off when the AC unit is calling for heat. When the AC unit calls 
   for heat the cooling should stop and heating comes from the 
   running servers.

   HVAC man suggested we could turn off 1 AC unit to "warm" the room.
   I will leave this decision for op.

   HVAC man has issued a WO with Phy Plant to repair this problem.

						--john c 6-8 