The following shutdown request for Bldg. 12 East (all floors) on 7/6 is
for your information and comment. Would you please let me know if this
meets with your approval or not.
Thanks very much.
Andrea Nichols
Operations Center
8-7872
> Status: Normal
> Building: 12 East - All floors
> Date: 7/6/98
> Day: Monday
> Time: 7:00 AM - 3:00 PM
> System: Supply ventilation, supply cooling, supply heating, exhaust
> laboratory air and exhaust general air
> Duration: 8 hours
> Reason:
> to remove old outside air dampers and install new outside air dampers.
>
> Effect:
> Loss of supply ventilation, supply cooling (outside air), supply
> heating, exhaust laboratory air and exhaust general air. This will not
> affect air conditioning.
>
>