[42723] in Hotline Meeting
Re: E40 Roof Water Overflow:
daemon@ATHENA.MIT.EDU (Jonathon Weiss)
Tue Apr 7 04:22:54 1998
From: Jonathon Weiss <jweiss@MIT.EDU>
To: "Louis A. Isgur" <larugsi@MIT.EDU>
Cc: op@MIT.EDU, network@MIT.EDU, dcns-cluster@MIT.EDU, hotline@MIT.EDU
In-Reply-To: Your message of "Tue, 07 Apr 1998 00:37:04 EDT."
<199804070437.AAA08470@killer.MIT.EDU>
Date: Tue, 07 Apr 1998 04:22:48 EDT
At around 1:30 Don checked out the temp in 008 and found that it was
still at 71 (of course he neglected to find me first, so he set off
the alarm). A little wile later CPs set off the alarm again (and
appearantly bolted teh deadbolt after checking the room (I unbolted
it)), appearantly having not gotten the message that it was plant who
set off the alarm the first time (Don said he'd called). Don also
said that the new ETA fro the FCS system was about 4 hours. Based on
the fact that 008 was remaining at a constant temp., and that the
chilled water plant seemed to be operating reasonable, modulo having
the cooling tower water supply shut off (there was plenty of water in
the system, and plant was going to keep an eye on it until they can
fix whatever problem caused the initial problem) I told Don I didn't
see a need for him to check 008 again tonight, unless he found another
problem with the chilled water plant. I just checked 008 and it had
dropped to 70, so I really don't think there is a problem here. If
people are feeling paranoid they can check 008 when they get in.
Jonathon